-20-
Address 07: Zone 5 Definition
*
Address 08: Zone 6 Definition
*
Address 09: Zone 7 Definition
*
Address 10: Zone 8 Definition
*
Address 11: Entry Delay Time
The entry delay timer determines the amount of time the user has to disarm the system
before an alarm is activated. The entry delay is only initiated if the premises are entered
through a zone defined as ‘perimeter with delay’. Enter a hexadecimal value between 1 and
255 seconds at this address using the hexadecimal conversion chart in Appendix A.
Address 12: Exit Delay Time
The amount of time the user has to leave the premises after arming is determined by the
exit delay timer. An open zone will not activate an alarm during this period. Enter a
hexadecimal value between 1 and 255 seconds at this address using the hexadecimal
conversion chart in Appendix A.
Address 13: Bell Cut-Off Time
The bell cut-off is the period of time that the bell or siren will be activated after an alarm
has occurred. Enter a value between 1 and 5 minutes at this address.
Address 14: PGM Options
The PGM (Programmable Output) can be used for indication of certain status or trouble
conditions. When the PGM output is activated terminal 9 switches to ground. Choose the
PGM output setting from the following table.
Value Name Activated By Deactivated By
00 PGM Disabled ------------------------
01 Arm/Disarm System Armed System Disarmed
02 Entry/Exit Entry/Exit Tone Follower Entry/Exit Tone Follower
04 Communication System in Communication End of Communication
08 AC Loss AC Loss AC Restore
10 Bell Follower Bell Follower Bell Follower
20 Duress Duress Code (deactivated after 2 seconds)
40 Alarm System in alarm Arm/Disarm/ Bell Cancel/
View log
†
80 Arm/Disarm
Tone
Momentary Activation (Arm – 1 Tone; Disarm – 2 Tones)
Note: If using Zone 1 as a dedicated fire zone, the PGM output is used to reset smoke
detector power and cannot be used in any of the modes listed above.
*
This address is only relevant to Penta Plus XL.
†
To deactivate the PGM output, the relevant log must be viewed.