4.4: Periodic Test Timer Reset
The control panel sends the periodic test event code (address 57) to the central station
once every 24 hours. The first transmission of this code is sent 12 hours after power is
applied to the control panel. If a different time is required, you can program the control
panel to send the first periodic test message 24 hours after the periodic test timer is
reset.
To reset the periodic test timer:
1. Press
4, 7 to enter programming mode.
2. Enter the Installer Code; the Armed LED lights up and the System LED flashes.
3. Enter
99; the periodic test timer is reset and the periodic test code is sent to the
central station.
4. Press
# to exit programming mode.